SetPoint 501sLiterature SetPoint 501 and 501s Controllers Installationand Operation ManualControl Microprocessor PI control; This is not a safety(limi
Table of ContentsSection 1 — Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Section 2 — InstallationGetting Ready . . . .
1iiSection 1 — IntroductionSection 1 IntroductionThe SetPoint 501 and 501s Controllers are microprocessor-based controlsthat are designed to sense the
Section 2 InstallationGetting ReadyCheck the contents of this package. If any contents listed below are missing or damaged, please contact your Uponor
5. If the controller is mounted to a 2x4 electrical box, order a Cover Platefor the 500 Series Controllers (part number A3040007). This platemounts to
Optional Sensors (501s Only)Each controller has a single built-in sensor to measure air temperature. In addition to this built-in sensor, the SetPoint
Section 3 Navigating the MenusView MenuROOM TARGETThis displays the current desired air temperaturefor the space (one active air sensor required). Thi
Section 4 TroubleshootingError MessagesE01The controller was unable to read a piece of information stored in its memory and was requiredto load the fa
Section 5 Technical DataSetPoint 501Literature SetPoint 501 and 501s Controllers Installationand Operation ManualControl Microprocessor PI control; Th